HXGN-12 High voltage ring network cabinet
HXGN-12 series switch cabinet is suitable for use in ring network or terminal power supply system of 3.6-12KV、AC 50HZ, as an indoor complete distribution equipment to accept and distribute power, it is also suitable for substations.
Main characteristics:
1.The load switch is independent, internal filling with sulfur hexafluoride gas as insulating medium, long life, highly configured, pollution-free, less maintenance.
2. The cabinet shell is made of high quality aluminum zinc plate, with characteristics of anti-corrosion, anti- oxidation, and novel appearance.
3. Spring energy storage operation, three-phase automatic tripping, integrated “five- prevents” interlocking and operating mechanism, safe and reliable linkage
4. Ring network cabinet can easily constitute ring network power supply units and other connection modes, with good expansibility.
5. Adopting sulfur hexafluoride load switch, with safe and reliable performance, no oil, non-toxic, no fire and explosion danger
Technical Parameters
No. |
Description |
Unit |
Specification |
|||||||
1 |
Rated current |
A |
630 |
1250 |
||||||
2 |
Rated voltage |
kV |
12 |
|||||||
3 |
Rated frequency |
Hz |
50/60 |
|||||||
4 |
Rated insulation level |
Power frequency withstand voltage (1min) |
Pole to earth/ between poles |
kV |
42 |
|||||
|
Between open contacts |
kV |
48 |
|||||||
Lightning impulse withstand voltage |
Pole to earth/ between poles |
kV |
75 |
|||||||
Between open contacts |
kV |
85 |
||||||||
5 |
Loading switch |
Rated current |
A |
630 |
1250 |
|||||
Rated short-time withstand current |
kA |
20 |
||||||||
Rated peak withstand current |
kA |
50 |
||||||||
Rated short-circuit making current |
kA |
50 |
||||||||
Closing speed |
m/s |
≥6 |
||||||||
Opening speed |
m/s |
4.5-6 |
||||||||
3-phase Non-synchronous opening |
ms |
10 |
||||||||
3-phase Non-synchronous closing |
ms |
10 |
||||||||
Turning degree |
deg |
120 |
||||||||
Breaking distance |
mm |
228 |
||||||||
6 |
Earthing switch |
Rated peak withstand current |
kA |
50 |
||||||
Rated short-circuit making current |
kA |
50 |
||||||||
Closing operation torque |
N.m |
≤60 |
||||||||
Opening operation torque |
N.m |
≤100 |
||||||||
Rated peak withstand current |
kA |
50 |
||||||||
Rated short-circuit making current(peak) |
kA |
50 |
||||||||
7 |
Earthing switch |
Rated loading breaking current |
kA |
630 |
1250 |
|||||
Rated closing breaking current |
kA |
630 |
1250 |
|||||||
Rateline-charging breaking current |
A |
10 |
||||||||
8 |
Rated short-circuit breaking current |
kA |
31.5 |
|||||||
9 |
Rated transferring current |
A |
1250 |
|||||||
10 |
Auxiliary/control circuit power frequency withstand current |
kA |
2 |
|||||||
11 |
Central distance between poles |
mm |
170(210) |
|||||||
12 |
Clearance between poles/pole to earth |
mm |
≥125 |
|||||||
13 |
Main circuit resistor |
Ω |
<105 |
|||||||
14 |
Mechanical life |
|
2000 times |
|||||||
15 |
Protection class |
|
IP2X |
|||||||
16 |
Overall dimension |
HXGN□-10/630 |
mm |
650X900X2000 |
||||||
HXGN□-10(RD)/80-31.5 |
mm |
700X900X2000 |
||||||||
17 |
Combinations |
Max rated current of fuse |
A |
100 |
||||||
Rated transferring current |
A |
1500(2000) |
||||||||
Rated short-circuit breaking current |
kA |
31.5 |
||||||||
Rated capacity of the transformer |
kVA |
1250 |
||||||||
18 |
Operation voltage |
V |
AC/DC 110/220 |
|||||||
19 |
Rated main busbar current |
A |
630 |
|||||||
20 |
If indoor vacuum load switch is used, the combinations as the main switch with rated transferring current 2000A, the mechanical life is 10000 times. |